
38
Model DCOutputFuse
12‐110‐1000‐B2 2x25A(AutoBlade)
12‐110‐1000‐B4
12‐110‐1800‐B4
3x25A(AutoBlade)
OverTemperatureProtection
Location Condition
ChargerTransformer
>95°C Max.Chargecurrentreducedtohalfoffullload
>100°C Max.Chargecurrentreducedto0A
ACTransferRelay >70°C Systemshutdown(noauto‐reset)
Note:Max.chargecurrentresumesnormallevelwhenChargerTransformersensor
temperaturedropsbelow90°C
Location
Warning(°C)
Errorcode/Audio
alarm
Shutdown(°C)
ErrorCode/Audio
alarm
On Off On Off
RectifierDiode >90 <88 E07/
Beep@0.33Hz
>95 <80 E04/
Beep@1Hz
Extrusion >63 <60 >60 <56
Note:Overtemperatureshutdownofthesesensorsisautoreset.Sensortemperature
toleranceis+/‐5°C
ReverseBatteryProtection
Model DCInputFuse
12‐110‐1000‐xx 4x30A(AutoBlade)
12‐110‐1800‐xx 8x30A(AutoBlade)
Note:ReversepolarityonDCInputwillopentheDCinputandfaultindicationfuses.Fusesarenon‐
replaceable,exceptatfactory.
Komentarze do niniejszej Instrukcji